Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Reverse Disable

Stop drive before changing this
parameter.
Enables/disables the function that
allows the direction of the motor
rotation to be changed. The reverse
command may come from a digital
command or serial command. All
reverse inputs including two-wire Run
Reverse will be ignored with reverse
disabled.
0 = Disabled
1 = Enabled

Parameter Number

195

Related Parameters

106

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Flying Start En

Sets the condition that allows the
drive to reconnect to a spinning motor
at actual RPM.
0 = Disabled
1 = Enabled

Parameter Number

196

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Compensation

Enables/disables correction options
that may improve problems with
motor instability,
0 = Disabled
1 = Electrical (Default)
Some drive/motor combinations have
inherent instabilities which are
exhibited as non-sinusoidal motor
currents. This setting attempts to
correct this condition
2 = Mechanical
Some motor/load combinations have
mechanical resonances which can be
excited by the drive current regulator.
This setting slows down the current
regulator response and attempts to
correct this condition.
3 = Both

Parameter Number

197

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

3

Default Value

1