Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Anti-bounce OFF Delay

This parameter allows the installer to
program a time duration before an
input is reported “OFF” (Anti-bounce).

Parameter Number

31

Access Rule

GET/SET

Data Type

UINT

Group

User I/O Config.

Units

ms

Minimum Value

0

Maximum Value

65

Default Value

0

In Sink/Source

This parameter allows the installer to
program the inputs to be sink or
source.
0 = Sink
1 = Source

Parameter Number

32

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltState

This parameter in conjunction with
Parameter 34 (OutA Pr FltValue)
defines how Output A will respond
when a protection trip occurs.
0 = Goto Pr FltValue
1 = Ignore Pr Flt
When set to “1”, Output A continues to
operate as command via the network.
When set to “0”, Output A will open or
close as determined by setting in
Parameter 34.

Parameter Number

33

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutA Pr FltValue

This parameter determines the state
the Output A assumes when a trip
occurs and Parameter 33 (OutA Pr
FltState) is set to “0”.
0 = Open
1 = Close

Parameter Number

34

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0