Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

125

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

User I/O Configuration Group

Str Net FltValue

This parameter determines how the
starter will be commanded in the
event of a fault. State the Starter will
go to on a Net Flt if Parameter 26 (Str
Net FltState) = 0 (Goto Fault Value).
0 = OFF
1 = ON

Parameter Number

27

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Str Net IdlState

This parameter in conjunction with
Parameter 29 (Str Net IdlValue)
defines how the starter will respond
when a network is idle as determined
by Parameter 29.
0 = Goto Idle Value
1 = Hold Last State

Parameter Number

28

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Str Net IdlValue

This parameter determines the state
that starter assumes when the
network is idle and Parameter 28 (Str
Net IdlState) is set to “0”.
0 = OFF
1 = ON

Parameter Number

29

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Anti-bounce On Delay

This parameter allows the installer to
program a time duration before an
input is reported “ON” (Anti-bounce).

Parameter Number

30

Access Rule

GET/SET

Data Type

UINT

Group

User I/O Config.

Units

ms

Minimum Value

0

Maximum Value

65

Default Value

0