Chapter 11, Specifications for ethernet/ip, Bulletin 280e/281e – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 239: Chapter

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

239

Chapter

11

Specifications for EtherNet/IP

Bulletin 280E/281E

Electrical Ratings

UL/NEMA

IEC

Power Circuit

Rated Operation Voltage

200…575V

200…575V

Rate Insulation Voltage

600V

600V

Rated Impulsed Voltage

6 kV

6 kV

Dielectric Withstand

2200V AC

2500V AC

Operating Frequency

50/60 Hz

50/60 Hz

Utilization Category

N/A

AC-3

Protection Against Shock

N/A

IP2X

Rated Operating Current Max.

280_-____-10A-* ➊

1.2 A

280_-____-10B-* ➊

2.5 A

280_-____-10C-* ➊

5.5 A

280_-____-25D-* ➊

16 A

Control Circuit

Rated Operation Voltage

24V DC (+10%, –15%) A2 (should be grounded at voltage source)

Rate Insulation Voltage

250V

250V

Rated Impulsed Voltage

4kV

Dielectric Withstand

1500V AC

2000V AC

Overvoltage Category

III

Operating Frequency

50/60 Hz

Short Circuit

Protection

Short Circuit Protection Device

(SCPD) Performance Type 1

Current Rating

Voltage

480Y/277V

480Y/480V

600Y/347V

600V

0.24…1.2 A

Sym. Amps rms

65 kA

65 kA

30 kA

30 kA

0.5…2.5 A

1.1…5.5 A

3.2…16 A

30 kA

30 kA

30 kA

30 kA

SCPD List

Size per NFPA 70 (NEC) or NFPA 79 for Group Motor Applications

See

Contactor Life Load Curves on page 244

Advertising