Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 185

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
185
Bulletin 280E/281E/284E Programmable Parameters Chapter 7
PID Ref Sel
Stop drive before changing this
parameter.
Enables/disables PID mode and
selects the source of the PID reference.
Valid PID Ref Select for the Bulletin
284E ArmorStart are the following:
0 = PID Disable
1 = PID Setpoint
4 = Comm Port
5 = Setpnt Trim
8 = Comm Trim
Parameter Number
232
Related Parameters
138
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
—
Minimum Value
0
Maximum Value
9
Default Value
0
PID Feedback Sel
Valid PID Feedback Sel command for
the Bulletin 284E ArmorStart is the
following;
2 = Comm Port
Parameter Number
233
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
—
Minimum Value
0
Maximum Value
2
Default Value
0
PID Prop Gain
Sets the value for the PID proportional
component when the PID mode is
enabled by Parameter 232 (PID Ref
Sel).
Parameter Number
234
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.01
Minimum Value
0.00
Maximum Value
99.99
Default Value
0.01
PID Integ Time
Sets the value for the PID integral
component when the PID mode is
enabled by Parameter 232 (PID Ref
Sel).
Parameter Number
235
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 sec
Minimum Value
0.0 sec
Maximum Value
999.9 sec
Default Value
0.1 sec