Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

Chapter 2 Installation and Wiring

Terminal Designations

As shown in Figure 16, the ArmorStart Distributed Motor Controller contains
terminals for power, control, and ground wiring. Access can be gained by
removing the terminal access cover plate.

Figure 16 - ArmorStart Power and Control Terminal Connections
(applies to Bulletin 280E/281E and Bulletin 284E)

Control Power Wiring

ArmorStart EtherNet/IP utilizes 24V DC control power for communications
and I/O. The control power terminal connections are labeled A1, A2, and A3.
Switched power will supply the outputs. Unswitched power will supply logic
power and sensor inputs.

See Detail A

Detail A

Table 3 - Power, Control and Ground Terminal Designations

Terminal Designations

No. of Poles

Description

A1 (+)

2

Control Power Input

A2 (–)

2

Control Power Common

A3 (+)

2

Unswitched 24V Control

PE

2

Ground

1/L1

2

Line Power Phase A

3/L3

2

Line Power Phase B

5/L5

2

Line Power Phase C