Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Comm Loss Time

Sets the time that the drive remain in
communication loss before
implanting the option selected in
Parameter 205 (Comm Loss Action).

Parameter Number

206

Related Parameters

115, 205

Access Rule

GET/SET

Data Type

UINT

Group

Advanced Program Group

Units

0.1 sec

Minimum Value

0.1 sec

Maximum Value

60.0 sec

Default Value

15.0 sec

Slip Hertz @ FLA

Compensates for the inherent slip in
an induction motor. This frequency is
added to the commanded output
frequency based on motor current.

Parameter Number

214

Related Parameters

133

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 Hz

Minimum Value

0.0 Hz

Maximum Value

10.0 Hz

Default Value

2.0 Hz

Process Time Lo

Scales the time value when the drive
is running at Parameter 134
(Minimum Freq). When set to a value
other than zero, Parameter 110
(Process Display) indicates the
duration of the process.

Parameter Number

215

Related Parameters

110, 134

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Hz

Minimum Value

0.00

Maximum Value

99.99

Default Value

0.00

Process Time Hi

Scales the time value when the drive
is running at Parameter 135
(Maximum Freq). When set to a value
other than zero, Parameter 110
(Process Display) indicates the
duration of the process.

Parameter Number

216

Related Parameters

110, 135

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Hz

Minimum Value

0.0

Maximum Value

99.99

Default Value

0.00