Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 294

Advertising
background image

294

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

Appendix B CIP Information

115

Get

Warning Status

WORD

Bits 0…1 = Reserved
Bit 2 = PL Warning (does not apply for Ethernet version)
Bit 3 = Reserved
Bit 4 = PR Warning (does not apply for Ethernet version)
Bit 5 = CP Warning
Bit 6 = I/O Warning
Bit 7 = Reserved
Bit 8 = PI Warning (does not apply for Ethernet version)
Bit 9 = DN Warning
Bits 10…12 = Reserved
Bit 13 = HW Warning
Bits 14…15 = Reserved

124

Get/Set

Trip Enable

WORD

Bit enumerated trip enable word

130

Get/Set

Trip Reset Mode

BOOL

0 = Manual, 1 = Auto

131

Get/Set

Trip Reset Level

USINT

0 = 100%, Default = 75

150

Get/Set

High Speed Ena

BOOL

0 = Disable, 1 = Enable

151

Get

Base Enclosure

WORD

Bit 0 = IP67
Bit 1 = NEMA 4x
Bits 2…15 Reserved

152

Get

Base Options

WORD

Bit 0 = Output Fuse
Bit 1 = Safety Monitor
Bit 2 = CP Fuse Detect
Bits 3…7 = Reserved
Bit 8 = 10A Base
Bit 9 = 25A Base
Bit 10…15 = Reserved

153

Get

Wiring Options

WORD

Bit 0 = Conduit
Bit 1 = Round Media
Bits 2…15 = Reserved

Attribute ID

Access Rule

Name

Data Type

Value

Advertising