Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Figure 70 - Start Boost

Brake Voltage

Sets the frequency where brake
voltage is applied when Parameter
184 (Boost Select) = 0 (Custom
V/Hz) and Parameter 225 (Torque Perf
Mode) = 0 (V/Hz).

Parameter Number

186

Related Parameters

131, 132, 134, 135, 184, 185, 187,

188, 225

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

1.1%

Minimum Value

0.0%

Maximum Value

100.0%

Default Value

25.0%

Brake Frequency

Sets the frequency where brake
frequency is applied when Parameter
184 (Boost Select) = 0 (Custom V/Hz)
and Parameter 225 (Torque Perf
Mode) = 0 (V/Hz).

Parameter Number

187

Related Parameters

131, 132, 134, 135, 184, 185, 186,

188, 225

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 Hz

Minimum Value

0.0 Hz

Maximum Value

400.0 Hz

Default Value

15.0 Hz

Parameter 131 (Motor NP Volts)

Parameter 188 (Maximum Voltage)

Parameter 134 (Minimum Freq)

Parameter 187 (Break Frequency)

Parameter 132 (Motor NP Hertz)

Parameter 135 (Maximum Freq)

Frequency

Voltage

Par

amet

er 1

86 (Br

eak

Voltage)

Par

amet

er 1

86

(Star

t B

oost)