Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 200

200
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
215
Process Time Lo
Scales the time value when the drive is running at Parameter 134
(Minimum Freq). When set to a value other than zero, Parameter
110 (Process Display) indicates the duration of the process.
0.00
Drive Advanced Setup
216
Process Time Hi
Scales the time value when the drive is running at Parameter 135
(Maximum Freq). When set to a value other than zero, Parameter
110 (Process Display) indicates the duration of the process.
0.00
Drive Advanced Setup
217
Bus Reg Mode
Enables the bus regulator.
1 = Enabled
Drive Advanced Setup
218
Current Limit 2
Maximum output current allowed before current limiting occurs.
Drive Rated
Amps x 1.5
Drive Advanced Setup
219
Skip Frequency
Sets the frequency at which the drive will not operate.
0.0 Hz
Drive Advanced Setup
220
Skip Freq Band
Determines the brand width around Parameter 219 (Skip
Frequency). Parameter 220 (Skip Freq Band) is split applying 1/2
above and 1/2 below the actual skip frequency.
0.0 Hz
Drive Advanced Setup
221
Stall Fault Time
Sets for the fault time that the drive will remain in stall mode
before a fault is issued.
0 = 60 Seconds
Drive Advanced Setup
222
Option not valid for Bulletin 284E ArmorStart.
223
Option not valid for Bulletin 284E ArmorStart.
224
Var PWM Disable
Enables/disables a feature that varies the carrier frequency for
the PWM output waveform defined by Parameter 191 (PWM
Frequency).
0 = Enabled
Drive Advanced Setup
225
Torque Perf Mode
Enables/disables sensorless vector control operation.
1 = Sensrls Vect
Drive Advanced Setup
226
Motor NP FLA
Set to the motor nameplate full load amps.
Drive Rated Amps
Drive Advanced Setup
227
Autotune
Provides an automatic method for setting Parameter 228
(IR Voltage Drop) and Parameter 229 (Flux Current Ref), which
affect sensorless vector performance.
0 = Ready/Idle
Drive Advanced Setup
228
IR Voltage Drop
Value of volts dropped across the resistance of the motor stator.
Based on Drive
Rating
Drive Advanced Setup
229
Flux Current Ref
Value of amps for full motor flux.
Based on Drive
Rating
Drive Advanced Setup
230
PID Trim Hi
Sets the maximum positive value that is added to a PID reference
when PID trim is used.
60.0
Drive Advanced Setup
231
PID Trim Lo
Sets the minimum positive value that is added to a PID reference
when PID trim is used.
0.1
Drive Advanced Setup
232
PID Ref Sel
Enables/disables PID mode and selects the source of the PID
reference.
0 = PID Disabled
Drive Advanced Setup
233
PID Feedback Sel
Valid PID Feedback Sel command for the Bulletin 284E
ArmorStart.
0 = 0-10V Input
Drive Advanced Setup
234
PID Prop Gain
Sets the value for the PID proportional component when the PID
mode is enabled by Parameter 232 (PID Ref Sel).
0.01
Drive Advanced Setup
235
PID Integ Time
Sets the value for the PID integral component when the PID mode
is enabled by Parameter 232 (PID Ref Sel).
0.1 Secs
Drive Advanced Setup
236
PID Diff Rate
Sets the value for the PID differential component when the PID
mode is enabled by Parameter 232 (PID Rel Sel).
0.01 (1/Secs)
Drive Advanced Setup
Table 29 - Parameter Descriptions
Parameter
Number
Parameter
Name
Description
Factory Default
Group