Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

215

Process Time Lo

Scales the time value when the drive is running at Parameter 134
(Minimum Freq). When set to a value other than zero, Parameter
110 (Process Display) indicates the duration of the process.

0.00

Drive Advanced Setup

216

Process Time Hi

Scales the time value when the drive is running at Parameter 135
(Maximum Freq). When set to a value other than zero, Parameter
110 (Process Display) indicates the duration of the process.

0.00

Drive Advanced Setup

217

Bus Reg Mode

Enables the bus regulator.

1 = Enabled

Drive Advanced Setup

218

Current Limit 2

Maximum output current allowed before current limiting occurs.

Drive Rated

Amps x 1.5

Drive Advanced Setup

219

Skip Frequency

Sets the frequency at which the drive will not operate.

0.0 Hz

Drive Advanced Setup

220

Skip Freq Band

Determines the brand width around Parameter 219 (Skip
Frequency). Parameter 220 (Skip Freq Band) is split applying 1/2
above and 1/2 below the actual skip frequency.

0.0 Hz

Drive Advanced Setup

221

Stall Fault Time

Sets for the fault time that the drive will remain in stall mode
before a fault is issued.

0 = 60 Seconds

Drive Advanced Setup

222

Option not valid for Bulletin 284E ArmorStart.

223

Option not valid for Bulletin 284E ArmorStart.

224

Var PWM Disable

Enables/disables a feature that varies the carrier frequency for
the PWM output waveform defined by Parameter 191 (PWM
Frequency).

0 = Enabled

Drive Advanced Setup

225

Torque Perf Mode

Enables/disables sensorless vector control operation.

1 = Sensrls Vect

Drive Advanced Setup

226

Motor NP FLA

Set to the motor nameplate full load amps.

Drive Rated Amps

Drive Advanced Setup

227

Autotune

Provides an automatic method for setting Parameter 228
(IR Voltage Drop) and Parameter 229 (Flux Current Ref), which
affect sensorless vector performance.

0 = Ready/Idle

Drive Advanced Setup

228

IR Voltage Drop

Value of volts dropped across the resistance of the motor stator.

Based on Drive

Rating

Drive Advanced Setup

229

Flux Current Ref

Value of amps for full motor flux.

Based on Drive

Rating

Drive Advanced Setup

230

PID Trim Hi

Sets the maximum positive value that is added to a PID reference
when PID trim is used.

60.0

Drive Advanced Setup

231

PID Trim Lo

Sets the minimum positive value that is added to a PID reference
when PID trim is used.

0.1

Drive Advanced Setup

232

PID Ref Sel

Enables/disables PID mode and selects the source of the PID
reference.

0 = PID Disabled

Drive Advanced Setup

233

PID Feedback Sel

Valid PID Feedback Sel command for the Bulletin 284E
ArmorStart.

0 = 0-10V Input

Drive Advanced Setup

234

PID Prop Gain

Sets the value for the PID proportional component when the PID
mode is enabled by Parameter 232 (PID Ref Sel).

0.01

Drive Advanced Setup

235

PID Integ Time

Sets the value for the PID integral component when the PID mode
is enabled by Parameter 232 (PID Ref Sel).

0.1 Secs

Drive Advanced Setup

236

PID Diff Rate

Sets the value for the PID differential component when the PID
mode is enabled by Parameter 232 (PID Rel Sel).

0.01 (1/Secs)

Drive Advanced Setup