Operation, Figure 2 - catalog number explanation for 284e – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 18

18
Rockwell Automation Publication 280E-UM001B-EN-P - July 2012
Chapter 1 Product Overview
Figure 2 - Catalog Number Explanation for 284E
Operation
The ArmorStart Distributed Motor Controllers can operate three-phase squirrel-
cage induction motors as follows:
Bulletin 280E/281E:
up to 10 Hp (7.4 kW) at 480V AC
Bulletin 284E: up to 5 Hp (3.0 kW) at 480V AC
ArmorStart EtherNet/IP Controllers accept 24V DC control voltage. The
control voltage will provide power to inputs (unswitched) and outputs
(switched). Unswitched control voltage is used to ensure no loss of sensor or
other field input status under normal operation.
g
Short Circuit Protection (Motor
Circuit Protector)
Code
Description
10
10 A Rated Device
25
25 A Rated Device
a
Bulletin Number
Code
Description
284
VFD Starter
d
Torque Performance Mode
Code
Description
V
Sensorless Vector Control
and Volts per Hertz
i
Option 1
Code
Description
3
Hand/Off/Auto Selector
Keypad with Jog Function
h
Control and 3-Phase Power Connections / Motor Cable Connection
(CR: Conduit/Round Media) or (RR: Round/Round Media)
Code
Description
Control Power
3-Phase Power
Motor Cable
CR
blank
Conduit Entrance
Conduit Entrance
3 m, unshielded
cordset male 90°
CR
N
Conduit Entrance
Conduit Entrance
3 m, shielded
cordset male 90°
CR
W
Conduit Entrance
Conduit Entrance
No cable
RR
blank
Round Media
(Male Receptacle)
Round Media
(Male Receptacle)
3 m, unshielded
cordset male 90°
RR
N
Round Media
(Male Receptacle)
Round Media
(Male Receptacle)
3 m, shielded
cordset male 90°
RR
W
Round Media
(Male Receptacle)
Round Media
(Male Receptacle)
No cable
284
E – F
V D2P3 D – 10 – CR – Option 1 – Option 2 – Option 3
a
b
c
d
e
f
g
h
i
j
k
b
Communications
Code
Description
E
EtherNet/IP
c
Enclosure Type
Code
Description
F
Type 4 (IP67)
e
Output Current
380…480V
Code
Description
D1P4
1.4 A, 0.4 kW, 0.5 Hp
D2P3
2.3 A, 0.75 kW, 1.0 Hp
D4P0
4.0 A, 1.5 kW, 2.0 Hp
D6P0
6.0 A, 2.2 kW, 3.0 Hp
D7P6
7.6 A, 3.3 kW, 5.0 Hp
j
Option 2
Code
Description
DB
blank DB Brake Connector
DB1
blank
Connectivity to IP67
DB Resistor
SB
blank
Source Brake
Contactor
SB
W
No cable
k
Option 3
Code
Description
EMI
EMI Filter
OC
Output Contactor
f
Control Voltage
Code
Description
Z
24V DC