Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Str Net FltState

This parameter in conjunction with
Parameter 27 (Str Net FltValue)
defines how the starter will respond
when a fault occurs as determined by
Parameter 27.
0 = Goto Fault Value
1 = Hold Last State
Allows Starter to hold last state or go
to FltValue on NetFaults.

Parameter Number

26

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Str Net FltValue

This parameter determines how the
starter will be commanded in the
event of a fault. State the Starter
will go to on a Net Flt if Parameter
26 (Str Net FltState) = 0 (Goto Fault
Value).
0 = OFF
1 = ON

Parameter Number

27

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Str Net IdlState

This parameter in conjunction with
Parameter 29 (Str Net IdlValue)
defines how the starter will respond
when a network is idle as determined
by Parameter 29.
0 = Goto Idle Value
1 = Hold Last State

Parameter Number

28

Access Rule

GET/SET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Str Net IdlValue

This parameter determines the state
that starter assumes when the
network is idle and Parameter 28 (Str
Net IdlState) is set to “0”.
0 = OFF
1 = ON

Parameter Number

29

Access Rule

GET

Data Type

BOOL

Group

Starter Protection

Units

Minimum Value

0

Maximum Value

1

Default Value

0