Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

175

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Figure 72 - Derating Guidelines Based on the PWM Frequency Setting

Clear a Type 1 Fault and Restart the Drive

1.

Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.

2.

Set Parameter 193 (Auto Rstrt Delay) to a value other than 0.

PWM Frequency

Sets the carrier frequency the PWM
output waveform. The Figure 72
provides derating guidelines based on
the PWM frequency setting.

Parameter Number

191

Related Parameters

224

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.l Hz

Minimum Value

2.0 Hz

Maximum Value

16.0 Hz

Default Value

4.0 Hz

Auto Rstrt Tries

Set the maximum number of times
the drive attempts to reset a fault and
restart.

Parameter Number

192

Related Parameter

155, 193

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

1

Minimum Value

0

Maximum Value

9

Default Value

0

52

64

76

88

100

96
92

84
80

72
68

60
56

1 2 3 4

5 6 7

8 9 10 11 12 13 14 15 16

Carrier Frequency (kHz)

% O

utput C

urr

en

t (

A)