Bulletin 280E/281E/284E Programmable Parameters Chapter 7
Figure 72 - Derating Guidelines Based on the PWM Frequency Setting
Clear a Type 1 Fault and Restart the Drive
1.
Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2.
Set Parameter 193 (Auto Rstrt Delay) to a value other than 0.
PWM Frequency
Sets the carrier frequency the PWM
output waveform. The Figure 72
provides derating guidelines based on
the PWM frequency setting.
Parameter Number
191
Related Parameters
224
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.l Hz
Minimum Value
2.0 Hz
Maximum Value
16.0 Hz
Default Value
4.0 Hz
Auto Rstrt Tries
Set the maximum number of times
the drive attempts to reset a fault and
restart.
Parameter Number
192
Related Parameter
155, 193
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
1
Minimum Value
0
Maximum Value
9
Default Value
0
52
64
76
88
100
96
92
84
80
72
68
60
56
1 2 3 4
5 6 7
8 9 10 11 12 13 14 15 16
Carrier Frequency (kHz)
% O
utput C
urr
en
t (
A)