Table 40 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 231

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

231

Troubleshooting Chapter 10

➊ See

Table 38

for Type description.

F81

Comm Loss

2

RS485 (DSI) port stopped
communicating.

30. Turn off using Parameter 205 (Comm Loss Action).
31. Replace starter module if fault cannot be cleared.

F100

Parameter

Checksum

2

The checksum read from the board does
not match the checksum calculated.

32. Set Parameter 141 (Reset To Defaults) to Option 1 (Reset Defaults).

F122

I/O Board Fail

2

Failure has been detected in the drive
control and I/O section.

33. Cycle power.
34. Replace starter module if fault cannot be cleared.

Table 39 - Bulletin 284E Faults – Parameters 107, 108, and 109 (Fault 1, 2 or 3)

No.

Fault

Type

Description

Action

Table 40 - Motor Does Not Start

Cause(s)

Indication

Corrective Action

No output voltage to the motor.

None

Check the power circuit.
Check the supply voltage.
Check all fuses and disconnects
Check the motor.
Verify that the motor is connected properly.
Verify that I/O Terminal 01 is active.
Verify that Parameter 136 (Start Source) matches your configuration.
Verify that

Parameter 195 (Reverse Disable) is not prohibiting movement.

Drive is Faulted

Flashing red status light

Clear fault.
Press Stop
Cycle power
Set Parameter 200 (Fault Clear) to Option 1 (Clear Faults).
Cycle digital input is Parameters 151…154 (Digital In x Sel) is set to Option 7, (Clear

Faults).

Table 41 - Drive Does Not Respond to Changes in Speed Command

Cause(s)

Indication

Corrective Action

No value is coming form the
source of the command.

The drive Run indicator is lit
and output is 0 Hz.

Check Parameter 112 (Control Source) for correct source.
If the source is an analog input, check wiring and use a meter to check for presence of

signal.

Check Parameter 102 (Commanded Freq) to verify correct command.

Incorrect reference source is
being selected via remote device
or digital inputs.

None

Check Parameter 112 (Control Source) for correct source.
Check Parameter 114 (Dig In Status) to see if inputs are selecting an alternate source. Verify

settings for Parameters 151…154 (Digital In x Sel).

Check Parameter 138 (Speed Reference) for the source of the speed reference. Reprogram

as necessary.

Table 42 - Motor and/or Drive Will Not Accelerate to Commanded Speed

Cause(s)

Indication

Corrective Action

Acceleration time is excessive.

None

Reprogram Parameter 139 (Accel Time 1) or Parameter 167 (Accel Time 2).

Excess load or short acceleration
times force the drive into current
limit, slowing, or stopping
acceleration.

None

Compare Parameter 103 (Output Current) with Parameter 189 (Current Limit1).
Remove excess load or reprogram Parameter 139 (Accel Time 1) or Parameter 167

(Accel

Time 2).

Check for improper setting of Parameter 184 (Boost Select).