Chapter 11 Specifications for EtherNet/IP

UL/NEMA

IEC

Environmental

Operating Temperature Range

–20…40 °C (–4…104 °F)

Storage and Transportation

Temperature Range

–25….85 °C (–13…185 °F)

Altitude

1000 m

Humidity

5…95% (on-condensing)

Pollution Degree

3

Enclosure Ratings

NEMA 4/12

IP67

Approximate Shipping Weight

18.1 kg (40 lbs)

Mechanical

Resistance to Shock

Operational 15

G

Non-Operational 30

G

Resistance to Vibration

Operational

1 G, 0.15 mm (0.006 in.) Displacement

Non-Operational

2.5 G, 0.38 mm (0.015 in.) Displacement

Power and Ground Terminals

Wire Size

Primary/Secondary Terminal:

#16…#10 AWG

Primary/Secondary Terminal:

1.0…4.0 mm2

Tightening Torque

Primary Terminal: 10.8 lb·in.

Secondary Terminal: 4.5 lb·in.

Primary Terminal: 1.2 N·m

Secondary Terminal: 0.5 N·m

Wire Strip Length

0.35 in. (9 mm)

Control Terminals

WireSize

#18…#10 AWG

1.0…4.0 mm2

Tightening Torque

6.2 lb·in.

0.7 N·m

Wire Strip Length

0.35 in. (9 mm)

Disconnect Lock Out

Maximum of 5/16 in. (8 mm) lock shackle or hasp. The hasp should not exceed

5/16 in. (8 mm) when closed, or damage will occur to disconnect guard.

Contactor Mechanical Life

CatNo 100-

Ops

C12

C23

280/1_-_12* Mil

13

280/1_-_23* Mil

13

Other Rating

EMC Emission Levels

Conducted Radio Frequency Emissions

10V rms Communications Cables

10V rms (PE)

150 kHz…80 MHz

Radiated Emissions

Class A

EMC Immunity Levels

Electrostatic Discharge

4 kV contact and 8 kV Air

Radio Frequency Electromagnetic Field

10V/m, 80 MHz…1 GHz

3V/m, 1.4 GHz…2 GHz

1V/m, 2.0 GHz …2.7 GHz

Fast Transient

2 kV (Power)

2 kV (PE)

1 kV (Communications and Control)

Surge Transient

1 kV (12) L-L, 2 kV (2) L-N (Earth)

Other Rating

Overload Current Range

280_-____-10A-*

0.24…1.2 A

280_-____-10B-*

0.5…2.5 A

280_-____-10C-*

1.1…5.5 A

280_-____-25D-*

3.2…16 A

Trip Classes ➊

10, 15, 20

Trip Rating

120% of Full Load current (FLC) Setting

Number of poles

3

➊Refer to

Motor Overload Trip Curves on page 243