Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

SW Current Trip

Enables/disables a software
instantaneous (within 100 ms)
current trip.

Parameter Number

198

Related Parameters

133

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 A

Minimum Value

0.0

Maximum Value

Drive rated amps x 2

Default Value

0.0 (Disabled)

Process Factor

Scales the output frequency value
displayed by Parameter 110 (Process
Display).
Output Freq x Process Factor = Process
Display

Parameter Number

199

Related Parameters

110

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1

Minimum Value

0.1

Maximum Value

999.9

Default Value

30.0

Fault Clear

Stop drive before changing this
parameter.
Resets a fault and clears the fault
queue. Used primarily to clear a fault
over network communications.
0 = Ready/Idle (Default)
1 = Reset Fault
2 = Clear Buffer (Parameters
107…109 (Fault x Code))

Parameter Number

200

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

2

Default Value

0

Program Lock

Protects parameters against change
by unauthorized personnel.
0 = Unlocked
1 = Locked

Parameter Number

201

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0