Diagnostics Chapter 9

h. Click on the Communication tab at the top of the window. Click on

the Browse button, select the ArmorStart that is in your project, and
click OK. This selects the ArmorStart as the device you are going to
send the reset message to.

i. You do not need to configure anything in the Tag tab. Click Apply and

then OK.

8.

Save your project. Download the project to the PLC and go Online.

9.

Inhibit the ArmorStart using the AOP:
a. Once online, open the ArmorStart's AOP and click on the Connection

tab. Select Inhibit Module from the options.

b. Click Apply, the following screen should pop-up. Click Yes. Then click

OK

to close out the AOP.