Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive
1.
Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.
2.
Set Parameter 193 (Auto Rstrt Delay) to 0.
ATTENTION: Equipment damage and/or personal injury may result if this parameter is
used in an inappropriate application. Do not use this function without considering
applicable local, national, and international codes, standards, regulations, or industry
guidelines.
Auto Rstrt Delay
Sets time between restart attempts
when Parameter 192 (Auto Rstrt Tries)
is set to a value other than zero.
Parameter Number
193
Related Parameters
192
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
0.1 sec
Minimum Value
0.0
Maximum Value
300.0 sec
Default Value
1.0 sec
Start at PowerUp
Stop drive before changing this parameter.
Enables/disables a feature that allows a Start or Run command to automatically cause the
drive to resume running at command speed after the drive input is restored. Requires a
digital input configured Run or Start and a valid start contact.
This parameter will not function if Parameter 136 (Start Source) is set to Option 4,
(2-W High Speed).
0 = Disabled
1 = Enabled
Parameter Number
194
Related Parameters
192
Access Rule
GET/SET
Data Type
UINT
Group
Drive Advanced Setup
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
ATTENTION: Equipment damage and/or personal injury may result
if this parameter is used in an inappropriate application. Do not use
this function without considering applicable local, national, and
international codes, standards, regulations, or industry guidelines.