Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault
without Restarting the Drive

1.

Set Parameter 192 (Auto Rstrt Tries) to a value other than 0.

2.

Set Parameter 193 (Auto Rstrt Delay) to 0.

ATTENTION: Equipment damage and/or personal injury may result if this parameter is
used in an inappropriate application. Do not use this function without considering
applicable local, national, and international codes, standards, regulations, or industry
guidelines.

Auto Rstrt Delay

Sets time between restart attempts
when Parameter 192 (Auto Rstrt Tries)
is set to a value other than zero.

Parameter Number

193

Related Parameters

192

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 sec

Minimum Value

0.0

Maximum Value

300.0 sec

Default Value

1.0 sec

Start at PowerUp

Stop drive before changing this parameter.
Enables/disables a feature that allows a Start or Run command to automatically cause the
drive to resume running at command speed after the drive input is restored. Requires a
digital input configured Run or Start and a valid start contact.
This parameter will not function if Parameter 136 (Start Source) is set to Option 4,
(2-W High Speed).
0 = Disabled
1 = Enabled

Parameter Number

194

Related Parameters

192

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0

ATTENTION: Equipment damage and/or personal injury may result
if this parameter is used in an inappropriate application. Do not use
this function without considering applicable local, national, and
international codes, standards, regulations, or industry guidelines.