Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 242

Advertising
background image

242

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

Chapter 11 Specifications for EtherNet/IP

Output Ratings – Sourced

from Control Circuit (A1/A2)

Rated Operation Voltage

26.4V DC

Rate Insulation Voltage

250V

Dielectric Withstand

1500V AC (UL)

2000V AC (IEC)

Operating Frequency

Solid state sourcing output

Type of Current

24V DC

Conventional Thermal Current Ith

0.5 A each, 1 A max. combined

Peak Output Current

Current limited 2-8 amps (5 amps nominal) @ 24V DC

Type of Contacts

Normally open (N.O.)

Number of Contacts

2

Load Types

Resistive or light inductive

Surge Suppression

Integrated diode, clamps @ 35V DC

Thermo-Protection

Integrated short circuit and over current protection

Maximum Cycle Rate

30 operations/minute capacitive and inductive loads

Maximum Blocking Voltage

35V DC

Maximum On-State Voltage @

Maximum Output

1.5V DC

Maximum Off-State Leakage Current

10 μA

Device Level Ring (DLR)

Beacon-based performance including IEEE 1588 end to end transparent clock

Fault Recovery

Ring recovery time is less than 3 ms for a 50 node network

Ethernet Port

EtherNet Receptacles

2 D-coded, 4-pin female M12 connectors

Ports

Embedded switch with 2 ports

IP Address

DHCP enabled by default

DHCP Timeout

30 s

Communication Rate

10/100 Mbs with auto negotiate half duplex and full duplex

Data

Transported over both TCP and UDP
Min. of 500 I/O packets/second (pps)
Supports up to 150 concurrent TCP sockets

Web Server

Embedded web server

Security

Login and password configurable

E-mail

Support Simple Mail Transfer Protocol (SMTP)

Configuration

Status, diagnostics, and configuration tabs

Device Connections

Supports scheduled (Class 1) and unscheduled (Class 3 & UCMM) connections

6 - Class 3 connections are supported simultaneously

Supports up to 2 Class 1 CIP connections [Exclusive owner (data) or listen-only]. One connection per PLC.

Listen only connection requires a data connection to be established.

Class 1 Connection API: 2…3200 ms, Class 3 Connection API: 100…10 000 ms

20 ms default (2 ms minimum)

3 concurrent Encapsulation sessions

TCP port supports 5 concurrent incoming connections

UL/NEMA