Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

155

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Output Current

Output Current present at T1, T2, T3.

Parameter Number

103

Access Rule

GET

Data Type

UINT

Group

Drive Display

Units

0.01

Minimum Value

0.00

Maximum Value

Drive rated amps x 2

Default Value

Read Only

Output Voltage

Output Voltage present at T1, T2, T3.

Parameter Number

104

Related Parameters

131, 184, 188

Access Rule

GET

Data Type

UINT

Group

Drive Display

Units

1V AC

Minimum Value

0

Maximum Value

480V

Default Value

Read Only

DC Bus Voltage

Present DC Bus voltage level

Parameter Number

105

Access Rule

GET

Data Type

UINT

Group

Drive Display

Units

1V DC

Minimum Value

Based on Drive Rating

Maximum Value

Default Value

Read Only

Drive Status

Present operating condition of the
drive
Bit 0 = Running
Bit 1 = Forward
Bit 2 = Accelerating
Bit 3 = Decelerating

Parameter Number

106

Related Parameter

195

Access Rule

GET

Data Type

Byte

Group

Drive Display

Units

Minimum Value

0

Maximum Value

1

Default Value

Read Only