Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

183

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

If the Autotune routine fails, an F80 SVC Autotune fault is displayed.

Motor NP FLA

Set to the motor nameplate full load
amps.

Parameter Number

226

Related Parameters

227

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 A

Minimum Value

0.1

Maximum Value

Drive rated amps x 2

Default Value

Drive rated amps

Autotune

Stop drive before changing this parameter.
Provides an automatic method for setting Parameter 228 (IR Voltage Drop) and Parameter
229 (Flux Current Ref), which affect sensorless vector performance. Parameter 226 (Motor
NP FLA) must be set to the motor nameplate full load amps before running the Autotune
procedure.
0 = Ready/Idle (Default)
1 = Static Tune
2 = Rotate Tune
Ready (0) – Parameter returns to this setting following a Static Tune or Rotate Tune.
Static Tune (1) – A temporary command that initiates a non-rotational motor stator
resistance test for the best possible automatic setting of Parameter 228 (IR Voltage Drop). A
start command is required following initiation of this setting. The parameter returns to
Ready (0) following the test, at which time another start transition is required to operate
the drive in normal mode. Used when motor cannot be uncoupled from the load.
Rotate Tune (2) – A temporary command that initiates a Static Tune followed by a
rotational test for the best possible automatic setting of Parameter 229 (Flux Current Ref). A
start command is required following initiation of this setting. The parameter returns to
Ready (0) following the test, at which time another start transition is required to operate
the drive in normal mode.

Parameter Number

227

Related Parameters

225, 226, 228, 229

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

3

Default Value

0

IMPORTANT

Used when motor is uncoupled from the load. Results may not be valid if a load is
coupled to the motor during this procedure.

ATTENTION: Rotation of the motor in an undesired direction can occur during this
procedure. To guard against possible injury and/or equipment damage, it is
recommended that the motor be disconnected from the load before proceeding.