Control module removal, Installation of control module – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 233

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

233

Troubleshooting Chapter 10

Control Module Removal

1.

Disconnect power by going to the control module and turning OFF the
At-Motor disconnect and performing lockout-tagout per your company
policy.

2.

Remove motor cable.

3.

Loosen the four mounting screws.

4.

Unplug the Control module from the base by pulling forward.

Installation of Control Module

5.

Install control module.

6.

Tighten four mounting screws.

7.

Install motor cable.

Figure 84 - Control Module Replacement

ATTENTION: To avoid shock hazard, disconnect main power before working on the
controller, motor, or control devices.

2

1

4

3

5

6

7

Motor Cable

30 lb•in./
3.39 N•m

Note: DeviceNet™ base module is shown.