150

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Miscellaneous Configuration Group

OutB Net FltValue

This parameter determines the state
that Output B assumes when a
network fault occurs and Parameter
41 (OutB Net FltState) is set to “0”.
0 = Open
1 = Close

Parameter Number

42

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB Net IdlState

This parameter in conjunction with
Parameter 44 (OutB Net IdlValue)
defines how Output B will respond
when the network is idle.
0 = Goto PrFlt Value
1 = Ignore PrFlt
When set to “0”, Output B will open or
close as determined by the setting in
Parameter 44.

Parameter Number

43

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

OutB Net IdlValue

This parameter determines the state
that Output B assumes when the
network is idle and Parameter 43
(OutB Net IdlState) is set to “0”.
0 = Open
1 = Close

Parameter Number

44

Access Rule

GET/SET

Data Type

BOOL

Group

User I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Network Override

This parameter allows for the local
logic to override a Network fault.
0 = Disable
1 = Enable

Parameter Number

8

Access Rule

GET/SET

Data Type

BOOL

Group

Misc. Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0