Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

InternalLinkStat

This parameter provides status of the
internal network connections.

Parameter Number

6

Access Rule

GET

Data Type

WORD

Group

Basic Status

Units

Minimum Value

0

Maximum Value

31

Default Value

0

Bit

Function:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

— — — — — — — — — — — — — — —

X

Explicit Connection

— — — — — — — — — — — — — —

X

I/O Connection

— — — — — — — — — — — — —

X

— —

Explicit Fault

— — — — — — — — — — — —

X

— — —

I/O Fault

— — — — — — — — — — —

X

— — — —

I/O Idle

X

X

X

X

X

X

X

X

X

X

X

— — — — —

Reserved

Starter Command

The parameter provides the status of
the starter command.

Parameter Number

7

Access Rule

GET

Data Type

WORD

Group

Basic Status

Units

Minimum Value

0

Maximum Value

255

Default Value

0

Bit

Function:

7

6

5

4

3

2

1

0

X

Run Fwd

X

Run Rev

X

Fault Reset

X

Jog Fwd

X

Jog Rev

X

Reserved

X

OutA

X

OutB