Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Comm Write Mode

Determines whether parameter
changes made over communication
port are saved and stored in Non-
Volatile Storage (NVS) or RAM only. If
they are stored in RAM, the values will
be lost at power-down.
0 = Save (Default)
1 = RAM Only

Parameter Number

264

Access Rule

GET/SET

Data Type

BOOL

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0

ATTENTION: Risk of equipment damage exists. If a controller is programmed to write
parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its
life cycle and cause the drive to malfunction. Do not create a program that frequently
uses configurable outputs to write parameter data to NVS unless Parameter 264 (Comm
Write Mode) is set to Option 1.

PID Invert Error

When set to “Inverted”, changes the
sign of the PID error. This causes an
increase in the drive output frequency
with PID Feedback greater than PID
Setpoint, and a decrease in drive
output frequency with PID Feedback
less than PID Setpoint.
0 = Not Inverted (Default)
1 = Inverted

Parameter Number

267

Access Rule

GET/SET

Data Type

BOOL

Group

Drive Advanced Setup

Units

Minimum Value

0

Maximum Value

1

Default Value

0