Control module led status and reset, Table 34, Table 33 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 212

Advertising
background image

212

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

Chapter 9 Diagnostics

Control Module LED
Status and Reset

The Control Module LED status and diagnostics consists of four status LEDs
and a Reset button. The following is a brief explanation of the operation of each
LED found on the Control Module.

The “Reset Button” is a local trip reset.

Table 33 - “Steady Red” MOD LED Status (Refer to Table 32.)

Fault Type

Description

0

EEPROM Fault

Non-volatile memory value out of range for a local parameter, or a write failure detected. This fault is also reflected by
a solid red MOD status LED.

1

Internal Comm2

The Internal communication connection has timed out. This fault is also reflected by a flashing red MOD status LED.

2

Hardware Fault

Internal diagnostics checks failed. This fault is also reflected by a solid red MOD status LED.

3

Control Module

An illegal or unsupported Control Module product code or revision has been detected. Also reported if no Control
Module is detected on power up. This fault is also reflected by a solid red MOD status LED.

4…15

Reserved

Reserved

Table 34 - Network Status Indicator

Indicator State

Summary

Requirement

Steady OFF

Not powered, no IP address

If the device does not have an IP address (or is powered OFF), the network status
indicator shall be steady OFF.

Flashing Green

No connections

If the device has no established connections, but has obtained an IP address, the
network status indicator shall be flashing green.

Steady Green

Connected

If the device has at least one established connection (even to the Message Router),
the network status indicator shall be steady green.

Flashing Red

Connection timeout

If one or more of the connections in which this device is the target has timed out,
the network status indicator shall be flashing red. This shall be left if only all timed
out connections are reestablished or if the device is reset.

Steady Red

Duplicate IP

If the device has detected that the IP addtress is already in use, the network status
indicator shal be steady red.

Flashing Red/Green

Self-test

While the device is performing its power up testing, the network status indicator
shall be flashing green/red.

Figure 81 - LED Status
Indication and Reset

Table 35 - Control Module LED Status Indication

LED

Definition

Recommended Action

Power

This LED will be illuminated solid green when
switched control power is present and with the
proper polarity.

Ensure 24V DC is present on A1 and A2. Check if the
local disconnect is in the OFF position.

Run

This LED will be illuminated solid green when a
start command and control power is present.

Ensure 24V DC is present on A1 and A3. Check if the
user is properly commanding to RUN via Instance
162 or 166.

Network

This bicolor LED is used to indicate the status of the
internal network connection.

See Table 34, Network Status Indicator table above
for additional information.

Fault

This LED is used to indicate the fault status of the
ArmorStart. When the unit is faulted, the unit will
respond with a specific blink pattern to identify the
fault.

See Table 36 and Table 37 below for additional
information.