Bulletin 280E/281E/284E Programmable Parameters Chapter 7

Table 20 - Digital Input Options

Option

Name

Description

0

Not Used

Terminal has no function but can be read over network communication via Parameter 114 (Dig In Status).

1

Acc2 & Dec2

When active, Parameter 167 (Accel Time 2) and Parameter 168 (Decel Time 2) are used for all ramp rates except Jog.

Can only be tied to one input.

2

Jog

When input is present, drive accelerates according to the value set in Parameter 179 (Jog Accel/Decel) and ramps to the value set in

Parameter 178 (Jog Frequency).

When the input is removed, drive ramps to a stop according to the value set in Parameter 179 (Jog Accel/Decel).

A valid Start command will override this input.

3

Aux Fault

When enable, an F2, Auxiliary Input fault will occur when the input is removed.

4

Preset Freq

(Parameters 151 and

152 Default)

Refer to Parameters 170…173 and 174…177.

5

Local (Parameter 153

Default)

Option not valid for Bulletin 284E ArmorStart.

6

Comm Port

This option is the default setting.

7

Clear Fault

When active, clears active fault.

8

RampStop,CF

Causes drive to immediately ramp to stop regardless of how Parameter 137 (Stop Mode) is set.

9

CoastStop,CF

Causes drive to immediately ramp to stop regardless of how Parameter 137 (Stop Mode) is set.

10

DCInjStop,CF

Causes drive to immediately begin a DC Injection stop regardless of how Parameter 137 (Stop Mode) is set.

11

Jog Forward

(Parameter 154

Default)

Drive accelerates to Parameter 178 (Jog Frequency) according to Parameter 179 (Jog Accel/Decel) and ramps to stop when input becomes
inactive. A valid start will override this command.

12

Jog Reverse

Drive accelerates to Parameter 178 (Jog Frequency) according to Parameter 179 (Jog Accel/Decel) and ramps to stop when input becomes
inactive. A valid start will override this command.

13

10V In Ctrl

Option not valid for Bulletin 284E ArmorStart.

14

20MA In Ctrl

Option not valid for Bulletin 284E ArmorStart.

15

PID Disable

Disabled PID function. Drive uses the next valid non-PID speed reference.

16

MOP Up

Increases the value of Parameter 169 (Internal Freq) at a rate 2 Hz per second. Default of Parameter 169 is 60 Hz.

17

MOP Down

Decreases the value of Parameter 169 (Internal Freq) at a rate 2 Hz per second. Default of Parameter 169 is 60 Hz.

18

Timer Start

Clears and starts the timer function. May be used to control the relay

19

Counter In

Starts the counter function. May be used to control the relay.

20

Reset Timer

Clears the active timer.

21

Reset Countr

Clears the active counter.

22

Rset Tim & Cnt

Clear active timer and counter.

23

Logic In1

Logic Function input number 1. May be used to control the relay (see Parameter 155, Options 11…14). May be used in conjunction with
StepLogic Parameters 240…247 (StpLogic X).

24

Logic In2

Logic Function input number 2. May be used to control the relay (see Parameter 155, Options 11…14). May be used in conjunction with
StepLogic Parameters 240…247 (StpLogic X).

25

Current Lmt2

When active, Parameter 218 (Current Limit 2) determines the drive current limit level.

26

Anlg Invert

Option not valid for Bulletin 284E ArmorStart.

27 ➊

Em Brk Rise

If EM Brake function enabled, this input releases the brake.

➊ Provides programmable control of Em Brk via digital input (1...4)