Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 198

Advertising
background image

198

Rockwell Automation Publication 280E-UM001B-EN-P - July 2012

Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

167

Accel Time 2

When active, sets the rate of acceleration for all speed increases
except for jog.

20.0 Secs

Drive Advanced Setup

168

Decel Time 2

When active, sets the rate of deceleration for all speed decreases
except for jog.

20.0 Secs

Drive Advanced Setup

169

Internal Freq

Provide the frequency command to drive when Parameter 138
(Speed Reference) is set to “1” (Internal Freq).

60.0 Hz

Drive Advanced Setup

170…177

Preset Freq 0
Preset Freq 1
Preset Freq 2
Preset Freq 3
Preset Freq 4
Preset Freq 5
Preset Freq 6
Preset Freq 7

Provides a fixed frequency command value when Parameters
151…154 (Digital In x Sel) is set to Option 4 (Preset
Frequencies).

See Table 22.

Drive Advanced Setup

178

Jog Frequency

Sets the output frequency when the jog command is issued.

10.0 Hz

Drive Advanced Setup

179

Jog Accel/Decel

Sets the acceleration and deceleration time when a jog command
is issued.

10.0 Secs

Drive Advanced Setup

180

DC Brake Time

Sets the length of time that DC brake current is injected into the
motor. Refer to Parameter 181 (DC Brake Level).

0.0 Secs

Drive Advanced Setup

181

DC Brake Level

Defines the maximum DC brake current, in amps, applied to the
motor when Parameter 137 (Stop Mode) is set to either Ramp or
DC Brake.

Drive Rated Amps x

0.05

Drive Advanced Setup

182

DB Resistor Sel

Used to set percent duty cycle for external dynamic braking.

0 = Disabled

Drive Advanced Setup

183

S Curve %

Sets the percentage of acceleration or deceleration time that is
applied to ramp as S Curve. Time is added, half at the beginning
and half at the end of the ramp.

0% (Disabled)

Drive Advanced Setup

184

Boost Select

Sets the boost voltage (% of Parameter 131 (Motor NP Volts))
and redefines the Volts per Hz curve. Active when Parameter 225
(Torque Perf Mode) = 0 (V/Hz). Drive may add additional voltage
unless Option 5 is selected.

8 = 5.0 (2.5 for 5 Hp

drives)

Drive Advanced Setup

185

Start Boost

Sets the boost voltage (% of Parameter 131 (Motor NP Volts))
and redefines the Volts per Hz curve when Parameter 184 (Boost
Select) = 0 (Custom V/Hz) and Parameter 225 (Torque Perf Mode)
= 0 (V/Hz).

2.5%

Drive Advanced Setup

186

Brake Voltage

Sets the frequency where brake voltage is applied when
Parameter 184 (Boost Select) = 0 (Custom V/Hz) and Parameter
225 (Torque Perf Mode) = 0 (V/Hz).

25.0%

Drive Advanced Setup

187

Brake Frequency

Sets the frequency where brake frequency is applied when
Parameter 184 (Boost Select) = 0 (Custom V/Hz) and Parameter
225 (Torque Perf Mode) = 0 (V/Hz).

15.0 Hz

Drive Advanced Setup

188

Maximum Voltage

Sets the highest voltage the drive will output.

Drive Rated Volts

Drive Advanced Setup

189

Current Limit 1

Maximum output current allowed before current limiting occurs.

Drive Rated Amps x

1.5

Drive Advanced Setup

190

Motor OL Select

Drive provides Class 10 motor overload protection. Setting 0…2

select the derating factor for I

2

t overload function.

0 = No Derate

Drive Advanced Setup

Table 29 - Parameter Descriptions

Parameter

Number

Parameter

Name

Description

Factory Default

Group

Advertising