Installation and Wiring Chapter 2
24V DC Control Power
• 24V DC (–15%, +10%)
• A1 = Switched +V
• A2 = Common for both switched and unswitched (–V)
• A3 = Unswitched +V
Input and Output Characteristics
• 5-pin female connectors (M12)
• 4 fixed inputs (two per connector) – software selectable sink or source
• 2 sourcing outputs DC (solid-state) – (one per connector)
Input and Output Power Connection
• Sensor Power will be sourced from +24V supplied from A3(+) and A2(–).
• Output power will be sourced from +24V supplied from A1(+) and A2(–).
• Max. current per output point is 0.5 A and is not to exceed 1.0 A total