Qos object, Class code 0x0048, Dpi fault object – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 297: Class code 0x0097

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

297

CIP Information Appendix B

The following common services will be implemented for the DLR Object.

Qos Object

CLASS CODE 0x0048

The following class attributes will be supported for the QoS Object.

A single instance (Instance 1) will be supported and it contains the following
instance attributes.

The following common services will be implemented for the QoS Object.

DPI Fault Object

CLASS CODE 0x0097

The DPI Fault Object is implemented in the DeviceNet Main Control Board.

Service Code

Implemented for:

Service Name

Class Instance

0x01

Yes

Yes

Get_Attribute_All

0x0E

Yes

Yes

Set_Attribute_Single

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Revision

UINT

1

Attribute ID

Access Rule

Name

Data Type

Value

1

Set

802 1Q Tag Enable

USINT

0 = Disable (Default)
1 - Enable

4

Set

DSCP Urgent

USINT

Default = 55

5

Set

DSCP Scheduled

USINT

Default = 47

6

Set

DSCP High

USINT

Default = 43

7

Set

DSCP Low

USINT

Default = 31

8

Set

DSCP Explicit

USINT

Default = 27

Service Code

Implemented for:

Service Name

Class Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single

Advertising