Starter display group (bulletin 280e/281e only) – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 130
130
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Starter Display Group (Bulletin 280E/281E only)
Keypad Mode
This parameter selects if the keypad
operation is maintained or
momentary.
0 = Maintained
1 = Momentary
Parameter Number
45
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Keypad Disable
This parameter disables all keypad
function except for the “OFF” and
“RESET” buttons.
0 = Not Disabled
1 = Disabled
Parameter Number
46
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Set to Defaults
This parameter if set to “1” will set the
device to the factory defaults (but will
not cause the ArmorStart to reboot).
0 = No Operation
1 = Set to Defaults
Parameter Number
47
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Phase A Current
This parameter provides the current of
Phase A measured n increments of
1/10
th
of an ampere.
Parameter Number
101
Access Rule
GET/SET
Data Type
INT
Group
Starter Display
Units
xx.x Amps
Minimum Value
0
Maximum Value
32767
Default Value
0