Bulletin 280E/281E/284E Programmable Parameters Chapter 7

➋When a Digital Input is set to "Accel 2 & Decel 2", and the input is active, that input overrides the settings in this table.

Input State of Digital In 1 (I/

O Terminal 05 when

Parameter 151 = 4)

Input State of Digital In 2 (I/

O Terminal 06 when

Parameter 152 = 4)

Input State of Digital In 3 (I/

O Terminal 07 when

Parameter 153 = 4)

Frequency

Source

Accel/Decel

Parameter

Used

1

0

1

175 (Preset Freq 5)

(Accel Time 3)/(Decel Time 3)

0

1

1

176 (Preset Freq 6)

(Accel Time 4)/(Decel Time 4)

1

1

1

177 (Preset Freq 7)

(Accel Time 4)/(Decel Time 4)

Jog Frequency

Sets the output frequency when the
jog command is issued.

Parameter Number

178

Related Parameters

135, 151…154, 179

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 Hz

Minimum Value

0.0

Maximum Value

400.0

Default Value

10.0

Jog Accel/Decel

Sets the acceleration and deceleration
time when a jog command is issued.

Parameter Number

179

Related Parameters

151…154, 178

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 sec

Minimum Value

0.1

Maximum Value

600.0

Default Value

10.0

DC Brake Time

Sets the length of time that DC brake
current is injected into the motor.
Refer to Parameter 181 (DC Brake
Level).

Parameter Number

180

Related Parameters

137, 181

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 sec

Minimum Value

0.0

Maximum Value

99.9

(Setting of 99.9 = Continuous)

Default Value

0.0

➊To activate 170 (Preset Freq 0) set 138 (Speed Reference) to "4" (Preset Freq).

➋When a Digital Input is set to "Accel 2 & Decel 2", and the input is active, that input overrides the settings in this table.