Appendix C Using DeviceLogix
Using parameters 170-173, set them to 0,10,30, and 60 respectively.
shows the preset frequencies 0-3.
Figure 101 - P170-173 Preset Frequency Settings
In this example DeviceLogix will receive data from the PLC program. The
communication and network overrides are disabled as shown below. Refer
to Appendix C for details when using the override function.
shows the DeviceLogix program. This allows the user to select one
of three predefined frequencies based on two network bits.