Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

153

Bulletin 280E/281E/284E Programmable Parameters Chapter 7

DrvIn Pr FltValue

This parameter determines the state
of Drive Digital Inputs 1…4, assumes
when a trip occurs and Parameter 49
(DrvIn Pr FltState) is set to “0”.
0 = Open
1 = Close

Parameter Number

50

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

DrvIn Net FltState

This parameter, in conjunction with
Parameter 52 (DrvIn Net FItValue),
defines how the Drive Digital
Inputs 1…4 will respond when a
network fault occurs. When set to “1”,
Drive Digital Inputs 1…4 hold to last
state occurs. When set to “0”, will go
to DrvIn Net FltValue as determined
by Parameter 52.
0 = Go to Fault Value
1 = Hold Last State

Parameter Number

51

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

DrvIn Net FItValue

This parameter determines the state
of Drive Digital Inputs 1…4 when a
network fault occurs and Parameter
51 (DrvIn Net FltState) is set to “0”.
0 = OFF
1 = ON

Parameter Number

52

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

DrvIn Net IdlState

This parameter, in conjunction with
Parameter 54 (DrvIn Net IdlValue),
defines how the Drive Digital Inputs
1…4 will respond when a network is
idle. When set to “1”, hold to last state
occurs. When set to “0”, will go to
DrvIn Net IdlState as determined by
Parameter 54.
0 = Go to Fault Value
1 = Hold Last State

Parameter Number

53

Access Rule

GET/SET

Data Type

BOOL

Group

Drive I/O Config.

Units

Minimum Value

0

Maximum Value

1

Default Value

0