Appendix d, Pid setup, Pid loop – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual

Page 327: Exclusive control, Appendix

Advertising
background image

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012

327

Appendix

D

PID Setup

PID Loop

The Bulletin 284E ArmorStart® Distributed Motor with sensorless vector control
has a built-in PID (proportional, integral, differential) control loop. The PID
loop is used to maintain a process feedback (such as pressure, flow, or tension) at a
desired set point. The PID loop works by subtracting the PID feedback from a
reference and generating an error value. The PID loop reacts to the error, based
on the PID Gains, and outputs a frequency to try to reduce the error value to 0.
To enable the PID loop, Parameter 232 (PID Ref Sel) must be set to an option
other than Option 0 (PID Disabled).

Exclusive Control and Trim Control are two basic configurations where the PID
loop may be used.

Exclusive Control

In Exclusive Control, the Speed Reference becomes 0, and the PID Output
becomes the entire Freq Command. Exclusive Control is used when
Parameter 232 (PID Ref Sel) is set to Option 1, 2, 3, or 4. This configuration
does not require a master reference, only a desired set point, such as a flow rate for
a pump.

Example

• In a pumping application, the PID Reference equals the Desired System

Pressure set point.

• The Pressure Transducer signal provides PID Feedback to the drive.

Fluctuations in actual system pressure, due to changes in flow, result in a
PID Error value.

• The drive output frequency increases or decreases to vary motor shaft

speed to correct for the PID Error value.

+

PID Prop Gain

PID Loop

PID Integ Time

PID Diff Rate

PID Enabled

PID Fdbk

PID Ref

PID

Error

+

+

+

PID

Output

Accel/Decel

Ramp

Freq

Command

Advertising