Ethernet link object, Class code 0x00f6 – Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 305

Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
305
CIP Information Appendix B
Ethernet Link Object
CLASS CODE 0x00F6
The following class attributes will be supported.
One instance of the Ethernet Link Object will be supported with the following
instance attributes.
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Revision
UINT
3
2
Get
Max Instance
UINT
2
3
Get
Number of Instances
UINT
2
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Interface Speed
UDINT
10 or 100 Mbit/Sec
2
Get
Interface Flags
DWORD
See ENet/IP Spec
3
Get
Physical Address
ARRAY of 6 USINTs
MAC Address
4 Get Interface
Counters
Struct of:
In Octets
In Ucast packets
In NUcast packets
In Discards
In Errors
In Unknown Protos
Out Octets
Out Ucast packets
Out NUcast packets
Out Discards
Out Errors
—
5 Get Media
Counters
Struct of:
Alignment Errors
FCS Errors
Single Collisions
SQE Test Errors
Deferred Transmits
Late Collisions
Excessive Collisions
MAC Transmit Errors
Carrier Sense Errors
Frame Too Long
MAC Receive Errors
—
6 Get/Set Interface
Control
Struct of:
Control Bits
Forced Interface Speed
—
7 Get
Interface
Type
USINT
—
8 Get
Interface
State
USINT
—
9 Get/Set
Admin
State
USINT
—
10 Get
Interface
Label
SHORT_STRING
Instance 1: Port 1
Instance 2: Port 2