Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 162

162
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Chapter 7 Bulletin 280E/281E/284E Programmable Parameters
Maximum Freq
Sets the highest frequency the drive
will output continuously.
Parameter Number
135
Related Parameter
101, 102, 113, 134, 135, 178,
185…187
Access Rule
GET/SET
Data Type
UINT
Group
Drive Setup
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400
Default Value
60.0
Start Source
Sets the control scheme used to start
the Bulletin 284E ArmorStart.
2 = 2-Wire
3 = 2-Wire Level Sensitive
4 = 2-Wire High Speed
5 = Comm Port (RS485 (DSI))
Parameter Number
136
Related Parameters
112 and 137
Access Rule
GET/SET
Data Type
UINT
Group
Drive Setup
Units
—
Minimum Value
0
Maximum Value
5
Default Value
5
Stop drive before changing this
parameter.
O
Stop drive before changing this
parameter.
O
Stop Mode
Valid Stop Mode for the Bulletin 284E ArmorStart are the following:
0 = Ramp, CF Ramp to Stop. Stop command clears active fault.
1 = Coast, CF Coast to Stop. Stop command clears active fault.
2 = DC Brake,CF DC Injection Braking Stop. Stop command clears active fault.
3 = DCBrkAuto, CF DC injection Braking with Auto Shutoff.
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time) or
Drive shuts off if the drive detects that the motor is stopped. Stop command clears
active fault.
4 = Ramp, Ramp to Stop
5 = Coast, Coast to Stop
6 = DC Brake, DC Injection Braking Stop
7 = DC BrakeAuto, DC Injection Stop with Auto Shutoff
Standard DC Injection Braking for value set in Parameter 180 (DC Brake Time)
or
Drive shuts off if current limit is exceeded.
8 = Ramp + EM B, CF Ramp to Stop with EM Brake Control. Stop command clears
active fault.
9 = Ramp + EM Brk Ramp to Stop with EM Brake Control.
Parameter Number
137
Related Parameters
136, 180…182, 205, 260, 261
Access Rule
GET/SET
Data Type
UINT
Group
Drive Setup
Units
—
Minimum Value
0
Maximum Value
9
Default Value
9