Rockwell Automation 284E ArmorStart with EtherNet/IP - User Manual User Manual
Page 300

300
Rockwell Automation Publication 280E-UM001B-EN-P – July 2012
Appendix B CIP Information
The table below lists Fault Codes, Fault Text, and Fault Help Strings for VFD
units.
36 Fault
36
—
37 Fault
37
—
38 Fault
38
—
39 Fault
39
—
40 Unknown
Fault
—
41 Fault
41
—
42 Fault
42
—
43 Fault
43
—
44 Fault
44
—
45 Fault
45
—
Table 50 Bulletin 284E
Fault Code
Fault Text
Help Text
1
Hdw Short Ckt
The built in 140M Circuit Breaker has tripped.
2
Fault 2
—
3
Motor Overload
The Load has drawn excessive current.
4
Drive Overload
150% load for 1 min. or 200% load for 3 sec. exceeded
5
Phase U to Gnd
A Phase U to Ground fault detected between drive and motor.
6
Phase V to Gnd
A Phase V to Ground fault detected between drive and motor.
7
Phase W to Gnd
A Phase W to Ground fault detected between drive and motor.
8
Phase UV Short
Excessive current detected between phases U and V.
9
Phase UW Short
Excessive current detected between phases U and W.
10
Phase VW Short
Excessive current detected between phases V and W.
11
Ground Fault
A current path to earth ground at one or more output terminals.
12
Stall
The drive is unable to accelerate the motor.
13
Control Pwr Loss
Indicates the loss of control power. This fault can be disabled.
14
Control Pwr Fuse
The Control Power Fuse has blown. Remove power and replace fuse.
15
Input Short
Flags a shorted sensor, input device, or input wiring mistake.
16
Output Fuse
The Output Fuse has blown. Remove all power and replace the fuse.
17
Over Temp
Indicates the operating temperature has been exceeded.
18
Heatsink OvrTmp
The Heatsink temperature exceeds a predefined value.
19
HW OverCurrent
The drive output current has exceeded the hardware limit.
20
SW OverCurrent
Programmed parameter 198 (SW Current Trip) has been exceeded.
21
A3 Power Loss
Unswitched (A3) Power was lost or dipped below the 12V DC threshold.
22
Internal Comm
Communication with the internal Power Flex drive has been lost.
23
Drive Comm Loss
The RS485 port on the internal Power Flex stopped communicating.
Table 49 - Bulletin 280E/281E
Fault Code
Fault Text
Help Text