Chapter 7 Bulletin 280E/281E/284E Programmable Parameters

Figure 71 - Overload Trip Curves

Maximum Voltage

Sets the highest voltage the drive will
output.

Parameter Number

188

Related Parameters

104, 185, 186, 187

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

1V AC

Minimum Value

20V AC

Maximum Value

Drive Rated Volts

Default Value

Drive Rated Volts

Current Limit 1

Maximum output current allowed
before current limiting occurs

Parameter Number

189

Related Parameters

133, 218

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

0.1 A

Minimum Value

0.1 A

Maximum Value

Drive rated amps X 1.8

Default Value

Drive rated amps X 1.5

Motor OL Select

Drive provides Class 10 motor
overload protection. Settings 0…2,

select the derating factor for I

2

t

overload function.
0 = No Derate
1 = Min. Derate
2 = Max. Derate

Parameter Number

190

Related Parameters

132, 133

Access Rule

GET/SET

Data Type

UINT

Group

Drive Advanced Setup

Units

1

Minimum Value

0

Maximum Value

2

Default Value

0

0

0

20

40

60

80

100

25 50 75 100 125 150 175 200

% of P132 [Motor NP Hertz]

No Derate

% of P133 Mot

or OL C

urr

en

t

0

0

20

40

60

80

100

25 50 75 100 125 150 175 200

% of P132 [Motor NP Hertz]

Min Derate

% of P133 Mot

or OL C

urr

en

t

0

0

20

40

60

80

100

25 50 75 100 125 150 175 200

% of P132 [Motor NP Hertz]

Max Derate

% of P133 Mot

or OL C

urr

en

t