Protection

8–5

Future Access (OEM Lock)

This option allows you to protect proprietary program data and algorithms. This
type of protection can be applied using any of the SLC 500 processors or
MicroLogix 1000 controllers. The protection takes effect only after the program is
downloaded to a controller. The protection does not allow online access to the
processor program unless a matching copy of the online processor program is
resident on the hard disk, in the Hand-Held Terminal (HHT), or in the memory
module of a Hand-Held Programmer (HHP).

Allow: Online access to the processor file and data table is unrestricted. This is the
default.

Disallow: Online access to the processor program is not permitted. You cannot:

monitor the program or create reports

enter or change the password

save the online processor file to disk

transfer the file from the processor memory to a memory module (SLC 500
processors only)

However, you can:

edit or view user data

clear the processor memory

create the processor configuration and data table reports (SLC 500 processors
only)

transfer the contents of a memory module into the processor memory (SLC 500
processors only)

restore (download) a different program to the controller

Note

If you lose or delete the offline copy of the program, you cannot access the program
in the controller. You must clear the controller memory and re-enter the program.

This feature is not recommended for use when the HHT is your only source of
program backup.

There is no “back door” access to get around this feature. If you intend to use this
feature, back up your program.