Monitoring Controller Operation

16–15

2.

Remove the fault by pressing

CONFIG

OFFLINE

CONFIG

CLR MAJ

FAULT

F10

. This clears words S:1/13, S:5, and

S:6. Refer to the Instruction Set Reference Manual for more information on
possible faults and their cause.

3.

Once the fault code is cleared, the code

0000

is displayed.

SLC 5/03 and SLC 5/04 processors - clearing these bits with the keyswitch in
the RUN position causes the processor to immediately enter the RUN mode.

4.

Re-enter the REMote Run or RUN mode. When you return to the RUN mode
all forces and latches are in effect.

If you are online with an SLC 5/03 and/or SLC 5/04 processor and the
keyswitch position is in RUN and you press the clear major fault function key,
the processor enters the RUN mode once you clear the fault.