Monitoring Controller Operation
16–15
2.
Remove the fault by pressing
CONFIG
OFFLINE
CONFIG
CLR MAJ
FAULT
F10
. This clears words S:1/13, S:5, and
S:6. Refer to the Instruction Set Reference Manual for more information on
possible faults and their cause.
3.
Once the fault code is cleared, the code
0000
is displayed.
SLC 5/03 and SLC 5/04 processors - clearing these bits with the keyswitch in
the RUN position causes the processor to immediately enter the RUN mode.
4.
Re-enter the REMote Run or RUN mode. When you return to the RUN mode
all forces and latches are in effect.
If you are online with an SLC 5/03 and/or SLC 5/04 processor and the
keyswitch position is in RUN and you press the clear major fault function key,
the processor enters the RUN mode once you clear the fault.