Configuring Your Programming Device for Online Communication

11–23

DF1 Half-Duplex Slave Device Configuration

The SLC 5/03 and SLC 5/04 processors support half-duplex protocol via RS-232
(channel 0 for both processors). In contrast to DF1 full-duplex, DF1 half-duplex
communication takes place in only one direction at a time. Refer to the Instruction
Set Reference Manual
for more information on Half-Duplex DF1 Slave protocol.

Note

It is not possible for APS and an SLC 5/03 or SLC 5/04 processor to communicate
using DF1 half-duplex protocol unless one of the processors or another device is
configured to be a DF1 half-duplex master.

F1

Port

COM1

Current Device

Half-Duplex Slave

F4

Terminal Address

0

F5

PROC Address

1

F7

Device/Modem/Half-Duplex Configuration

F9

Save to File

F9

Press a function key

SAVE TO

FILE

F5

PROC

ADDRESS

F1

PORT

F2

SELECT

DEVICE

F4

TERM

ADDRESS

ESC exits/Alt-U aborts changes

ONLINE CONFIGURATION

F7

DEVICE

CONFIG

Function Key

Description

[F1] Port

Toggles between COM1 and COM2. This field indicates

where the processor is connected to your computer. The

default is COM1.

[F2] Select Device

Toggles between the selected interface card and the interface

card selection menu.

[F4] Terminal Address

Allows selection of a terminal address as a node number.

Valid range is 0–254 decimal. The default is 0.

[F5] Processor Address

Allows selection of a processor address as a node number.

Valid range is 1–254 decimal. The default selection is 1.

[F7] Device Configuration

Allows you to select the configuration parameters for the

specified device.