Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 410

Advertising
background image

Preface

Advanced Programmming Software User Manual

A–16

Display Message

Recommended Action

Description

NOT A LADDER FILE

An attempt to jump to a ladder file was

made, but the file number specified is

not a ladder file.

Verify the operation and specify a valid

ladder file.

NOT ENOUGH MEMORY FOR

COMMUNICATION DRIVER

The software package tried to load files

that exceeded 128KBytes.

Retry the function and if necessary exit

and restart the software. If the error

continues validate the disk by running

the CHKDSK" from the DOS prompt.

ONLINE EDITING NOT AVAILABLE,

INVALID KEYSWITCH POSITION

Online editing is not allowed when the

SLC 5/03 or SLC 5/04 keyswitch is in the

Run position.

Change the keyswitch to the Remote or

Program position. Retry the function.

OPERAND MUST BE INDEXED

The operand for the current instruction is

not indexed.

Index the operand and retry the function.

OPERATOR ABORTED DIALUP

While going online with DF1 Full Duplex

through a 1770ĆKF3 and a modem the

[ESC] key was pressed.

Retry the function.

OUT OF DATA TABLE MEMORY

During program save or test edits an

error occurred while attempting to copy a

data table from the database to the

processor image.

The program is too large. Reduce the

program memory requirements.

OUT OF MEMORY IN PROCESSOR

IMAGE

Either 1) during program save or test

edits all available memory in the

processor image was used by the

program; or 2) the program is too big for

the processor.

The program is too large. Reduce the

program memory requirements.

OUT OF MEMORY IN PROGRAMMING

DEVICE

During program save or test edits all

available memory in the programming

device was used.

The program is too large. Reduce the

program memory requirements.

PARSE ERROR

Entry on line was an invalid file or rung

number.

Verify file or rung entry and retry the

function.

PLINK Errors

These errors indicate software package

problems.

Attempt to reinstall APS and call your

RSI representative.

POINT IS PROTECTED, FUNCTION

NOT AVAILABLE

An attempt to change the state of a

protected bit was made, either from the

online multiĆpoint list, or from a force

menu.

Informational message. No action

necessary.

PROBLEMS ENCOUNTERED DURING

ASSEMBLE/CANCEL EDITS

A problem exists with the database

assemble/cancel edits function.

Contact your local RSI representative.

PROCESSOR DATA VALUES MAY

HAVE CHANGED

During quick edits, when switching from

offline to online monitoring, the offline

data tables were downloaded.

Changes to the processor data tables

may occur if the offline data tables do

not match the online data tables. Verify

for the correct data tables.

Advertising