Fault Recovery Procedure

To remove a fault condition and return to the RUN or REMote Run mode, do the
following:

1.

Press

CONFIG

OFFLINE

CONFIG

ONLINE

F1

, then

CONFIG

OFFLINE

CONFIG

DATA

MONITOR

F9

. Press the letter

S

and then press

[ENTER]

.

The first screen of the status file contains the fault code and fault description.

Press function key or enter value, press Alt–H for help.
S:0/0 =
offline

no forces

formatted

decimal addr

File 09TEST

F7

F5

NEXT

FILE

SPECIFY

ADDRESS

ARITHMETIC FLAGS S:0 Z:0 V:0 C:0

PROCESSOR STATUS 00000000 00000000 SUSPEND CODE 0
PROCESSOR STATUS 00000000 00000001 SUSPEND FILE 0
PROCESSOR STATUS 00000000 00000000
WATCHDOG [x10 ms] 10
MINOR FAULT 00000000 00000000 LAST SCAN [x10 ms] 0
FAULT CODE 0000 FREE RUNNING CLOCK 00000000 00000000
FAULT DESCRIPTION:

MATH REGISTER 0000 0000

ACTIVE NODE LIST I/O SLOT ENABLES
0 10 20 30 0 10 20 30
11000000 00000000 00000000 00000000 11111111 11111111 11111111 11111111

PROCESSOR BAUD RATE (Channel 1) 19200 PROCESSOR ADDRESS: 1

F9

F10

F8

CLR MIN

FAULT

CLR MAJ

FAULT

PREV

FILE

F1

PAGE

UP

F2

PAGE

DOWN









 Word S:1. Bit S:1/13 in this word is the major fault bit. Cleared by

pressing

[F10] Clear Major Fault

.

 Word S:5. Minor fault bits. Cleared by pressing

[F9] Clear Minor

Fault

or

[F10] Clear Major Fault

.

 Word S:6. Fault code. Cleared by pressing

[F10] Clear Major

Fault

.

 Fault description. A textual description of the fault code. Cleared by

pressing

[F10] Clear Major Fault

.