Preface

Advanced Programmming Software User Manual

A–12

Display Message

Recommended Action

Description

ILLEGAL SYMBOL

During configuration of report options for

the cross reference report an illegal

starting or ending symbol was entered.

Enter a valid symbol and retry the

function.

IMMEDIATE FLOATING POINT IS NOT

SUPPORTED BY THIS PROCESSOR

A preĆSLC 5/03 Series B processor is

configured.

Either change the processor to an SLC

5/03 Series B or SLC 5/04 processor, or

change the ladder program to not

include floating point values.

IMMEDIATE FLOATING POINT VALUE

IS NOT ALLOWED

The instruction parameter does not

support floating point values.

Either change the processor to an SLC

5/03 Series C or SLC 5/04 processor, or

select a different instruction.

INCOMPATIBLE DEVICE

The version of the software is unable to

communicate with the requested device.

Contact your RSI representative.

INCORRECT BOARD ADDRESS OR

IRQ - DRIVER HAS SET CORRECT

VALUES

(This message only appears when one

1784ĆKT2 interface module is installed.)

When configuring the 1784ĆKT2

communication interface module, an

incorrect board address or IRQ was

entered.

No action required. The 1784ĆKT2

interface module sets the correct board

address or IRQ value.

INCORRECT COMMUNICATION

BOARD IRQ CONFIGURATION

The IRQ address for a 1784ĆKT2,

1784ĆKL, or 1784ĆKT interface module

was entered incorrectly in the online

configuration. This message also

appears when more than one 1784ĆKT2

interface modules are installed.

Verify the correct IRQ address on the

interface module and change the

parameter in the online configuration set

up. Retry the function.

INCORRECT COMMUNICATION

BOARD ADDRESS CONFIGURATION

The board address for a 1784ĆKL or

1784ĆKT interface module was entered

incorrectly in the online configuration.

This message also appears when more

than one 1784ĆKT2 interface module is

installed.

Verify the correct board address on the

interface module and change the

parameter in the online configuration set

up. Retry the function.

INPUT INVALID, PLEASE REENTER

Incorrect syntax entered.

Retry the function.

INPUT MIN. MUST BE LESS THAN

INPUT MAX.

An attempt was made to enter a Scale

with Parameters instruction having an

input minimum constant operand greater

than the input maximum constant

operand.

Either make the input maximum value

greater than the input minimum value, or

change one of the operands to a

nonĆconstant value.

INPUT, OUTPUT, AND STATUS FILES

CANNOT BE CONSTANT PROTECTED

An attempt to constant protect these

types of files was made.

Apply only static protection to these

types of files.

INSTRUCTION HAS NO OPERANDS

`Modify symbol' was selected, but the

instruction does not have any operands.

Informational message. No action

necessary.

INSTRUCTION HAS NO OPERANDS

TO RELATE TO SYMBOL

The instruction has operands, but none

of the operands support a symbol name.

ReĆenter the user instruction address.