Configuring Your Programming Device for Online Communication
11–29
1784-KT (DH+ Direct) and 1784-KT2 (DH+ Direct) Interface Cards
Use either the 1784-KT (DH
+
Direct) or 1784-KT2 (DH
+
Direct) interface cards to
connect an IBM compatible or IBM PS/2 microchannel computer directly to an
SLC 5/04 processor on a DH
+
link for programming. These interface cards share
the same configurable parameters.
Current Device
1784-KT (DH+ Direct)
F3
Connection
DIRECT
F4
Terminal DH
+
Address
0 (octal)
F5
SLC Node Address
1 (octal)
F7
IRQ
3
F8
Board Address
000011
F9
Save to File
F9
Press a function key
SAVE T0
FILE
F5
SLC
ADDRESS
F3
CONNECT
TYPE
F2
SELECT
DEVICE
F4
TERM
ADDRESS
ESC exits/Alt-U aborts changes
ONLINE CONFIGURATION
F7
IRQ
F8
BOARD
ADDRESS
Function Key
Description
[F2] Select Device
Toggles between the selected interface card and the interface card
selection menu.
[F3] Connect Type
Toggles between Direct and MultiĆDrop. Direct means that the terminal
has a termination resistor (last device on the DH
+
link). MultiĆDrop
means that the terminal does not have a termination resistor. The
default is Direct.
[F4] Terminal Address
Allows selection of a terminal address as a node number. Valid range is
0–77 octal. The default is 0.
[F5] SLC Address
Allows selection of a processor address as a node number. Valid range
is 0–77 octal. The default is 1.
[F7] IRQ
1784ĆKT
Allows you to select the IRQ on the board (3, 4, 5, and 7.) The default is
3. See the 1784ĆKT card user manual for details.
1784ĆKT2
Allows you to select the IRQ on the board (9, 10, 11, and 12.) The
default is 9. See the 1784ĆKT2 card user manual for details.