Types of online editing, 17œ5 – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 326

Advertising
background image

Online Editing

17–5

Types of Online Editing

The type of online editing is dependent on the SLC 5/03 or SLC 5/04 processor’s
keyswitch position and the processor’s mode. There are two types of online editing:

Program Online Editing — when the processor is in either PROG mode or REM
Program mode

Runtime Online Editing — when the processor is in either REM Test or REM
Run mode

The following table summarizes the SLC 5/03 and SLC 5/04 processor keyswitch
positions and modes that enable online editing.

Keyswitch Position

SLC 5/03 and SLC 5/04

Processor Mode

Editing Mode

RUN

Run

Not Available

PROGram

Program

Program Online Editing

REMote

REMote Program

Program Online Editing

REMote

REMote Test

Runtime Online Editing

REMote

REMote Run

Runtime Online Editing

Note

Online editing is not available when the keyswitch is in the RUN position. If you
attempt to perform an online edit with the keyswitch in the RUN position, the
message:

ONLINE EDITING NOT AVAILABLE, INVALID KEYSWITCH

POSITION

is displayed.

Use the online editing function while in the RUN mode to make minor changes
to the ladder program. We recommend developing your program offline since
ladder rung logic changes take effect immediately after testing your edits.
Improper machine operation may occur, causing personnel injury or
equipment damage.

Advertising