Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 273
Configuring Your Processor for Online Communication
13–23
To change the SLC 5/03 processor poll timeout value, do the following:
1.
At the Program Directory display, press
[F8] Monitor File
, then
[F7]
General Utility
, then
[F5] Channel Configuration
.
2.
Cursor to the System Mode Driver parameter and press [F10] Select Option
until “DF1 Half-Duplex Slave” is displayed.
3.
Press
[F4] CH0 System Configuration
. Cursor to the poll timeout
parameter and press
[F10] Select Option
. Enter the new value and
press
[ENTER]
.
You can also change the edit resource/file owner timeout value at this time.
4.
Press
[F1] Accept Edits
, then
[ESC]
,
[ESC]
,
[ESC]
and return to the
Program Directory display.
If you are using MSG instructions between SLC 5/03 processors, the MSG timeout
value shown in the control block may also need to be changed for reliable
slave-to-slave communication on the multi-drop network.