Function key [f10, Offline config – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual

Page 334

Advertising
background image

Online Editing

17–13

Online Editing cannot be performed while the edited rungs are executing. For
example, if you are testing edits and you want to make further changes, you must
either perform an untest edits or assemble edits.

If you proceed, the edits field on the status line changes from

TESTING

to

DISABLED

. For a Runtime Online Editing session, the processor executes rungs

not marked with edit zones and all rungs marked with delete or replace zones. Any
rungs marked with insert zones are not executed.

Note

Untesting edits does not restore the data table values that were altered when you
accepted the rung.

Function Key [F10]

This key toggles between Assemble Edits and Cancel Edits. The following section
describes its operation.

[F10] Assemble Edits

If you find that your changes are accomplishing proper machine operation, you can
make those changes a permanent part of your program by using the Assemble Edits
function. You can only assemble edits while edits are being tested. Assembling
edits places the online editing changes into the program and removes the edit zones
markers.

All rungs marked with insert edit zones are assembled into the ladder program
and the edit zone markers are removed.

All rungs marked with replace or delete edit zones are deleted from the ladder
program.

Press

CONFIG

OFFLINE

CONFIG

ASSEMBLE

EDITS

F10

. If you proceed, the edits field on the status line changes from

TESTING

to

NONE

. Edits are assembled into the program and the message:

CAUTION: VERIFY STATE OF OUTPUTS WITH DATA MONITOR

is

displayed.

When performing this function your scan time and interrupt latency can increase by
10 ms per scan.

Advertising