Preface – Rockwell Automation 9323-PA1E USER MANUAL APS 6.0 User Manual
Page 349

Preface
Advanced Programming Software User Manual
18–4
The keys available at the multi-point list menu perform the following functions:
Function Key
Description
[F1] Edit Fields
Accesses the multiĆpoint edit fields menu. See page 18-5.
[F2] Display Symbols/Address
Toggles between Display Symbols and Display Address.
[F3] Toggle State
If online: Toggles the state in the online data table of the bit
that is addressed by the current entry.
If offline: Toggles the state in the offline data table of the bit
that is addressed by the current entry.
This does not effect any force applied to the bit.
[F4] Protect
(Available only from the offline multiĆpoint list.)
Toggles an entry between read/write and readĆonly. If
readĆonly is selected the letter P appears after the point
number.
Once a bit is protected, and the offline multiĆpoint list contents
are copied to the online multiĆpoint list, the following is true
when viewing the online multiĆpoint list. You cannot:
S
toggle the state of the bit
S
edit the address
S
edit the on or off descriptions
S
install or remove forces
S
delete the entry
Note
Forces can still be enabled and disabled, since these
functions apply to all forces, both inputs and outputs,
and can include forces not shown on the multiĆpoint
list screen.
[F5] View Offline/Online
(Available only when online.)
It toggles between the offline multiĆpoint list and the online
multiĆpoint list.
[F6] Copy to Offline/Online
(Available only when online.)
If viewing the online multiĆpoint list, pressing this key copies
the contents of the online multiĆpoint list to the offline
multiĆpoint list. The online list remains displayed.
If viewing the offline multiĆpoint list, pressing this key copies
the contents of the offline multiĆpoint list to the online
multiĆpoint list. The offline list remains displayed.
[F7] Force
Allows you to access the multiĆpoint force menu. See page
[F10] Exit
Returns you to the previous menu. Offline multiĆpoint lists are
saved when you save the program.